Emerson 059542 is a 48 cubic inch Model H48 Filter Drier Core. This is used for High Acid and Water Removal and the recommendable refrigerants are CFC and HCFC Refrigerants.
Emerson Filter Cores are applicable for use in ADKS and STAS shells. They have exceptional acid capacities for normal system protection, or to effectively clean-up following a compressor burnout. Features water capacities to suit specific system conditions.
NOTE: Filter Drier cores are suitable for use with R-11 AND R-123 but filters are NOT. May not be used for BTAS.
Model No. | Water Capacity Drops of Water | |||||||||||||
059542 H48 |
R-12 | R-134a | R-22 | R-407C | R-404A/R-507 | R410A | R-502 | |||||||
75°F | 125°F | 75°F | 125°F | 75°F | 125°F | 75°F | 125°F | 75°F | 125°F | 75°F | 125°F | 75°F | 125°F | |
1020 | 688 | 676 | 538 | 597 | 436 | 445 | 285 | 721 | 535 | 380 | 226 | 643 | 475 | |
Water Capacities are based on Equilibrium Point Dryness (EPD): | 50 parts per million for R-134a, R404-A/R-410A R-407C 60 parts per million for R-22 15 parts per million for R-12 |
Size | 48 cubic inch |
---|---|
Refrigerant Type | CFC, HCFC |
Download Product Information:
Emerson Climate Filter Drier Cores and Filter Technical Sheet