Flow (CFH) Natural Gas - 0.65 Specific Gravity at 60°F with 1 in. W.C. Pressure Drop @ 1.25 PSI Inlet Pressure |
||||
DMV 702 | 1" | 1-1/4" | 1-1/2" | 2" |
1065 | 1277 | 1368 | 1430 |
Karl Dungs DMV-D Valve |
Flange Size | NPT Flange Part # |
Rp Flange Part # |
O-Ring & Bolt Kit Part # |
FRI Mounting Kit Part # |
Integral Filter & Strainer Replacement |
DMV 702/602 & 703/602 | 1” | 222-369 | 222-343 | 224-094 | 219-968 | 230-441 |
1 1/4” | 222-370 | 222-344 | 224-094 | 219-968 | 230-441 | |
1 1/2” | 222-003 | 221-884 | 224-094 | 219-968 | 230-441 | |
2” | 221-997 | 221-926 | 224-094 | 219-968 | 230-441 |
Model Number | Description |
210-319 | DIN-Electrical Connector |
224-253A | CPI 400 valve switch |
217-665A | Visual indicator |
225-047 | 1/4” NPT adapter |
225-043 | 1/2” NPT Pilot gas adapter: Check flow requirements |
219-008 | G1/8 Test nipple |
214-975 | Port 3 Pressure switch mounting adapter |
Operating Time | 100% duty cycle |
---|---|
Power Rating | 65 VA |
Electrical Ratings | 24 VDC |
Enclosure Rating | NEMA Type 12 |
Closing & Opening Time | < 1 s |
Ambient Temperature Rating | -40 °F to +150 °F (-40 °C to +65 °C) |
Maximum Body Pressure | 15 PSI (1000 mbar) |
Maximum Close Off Pressure | 7 PSI (500 mbar) UL, FM; 5 PSI ( 360 mbar) CSA |
Maximum Operating Pressure | 7 PSI (500 mbar) UL, FM; 5 PSI ( 360 mbar) CSA |
Electrical Connection | DIN connector with 3/4” NPT conduit adapter |