Mounting Position | Mount with the diaphragm in any vertical plane |
---|---|
Field Adjustable Operating Range | 0.07" w.c. to 12.0" w.c. |
Set Point Range | 0.05 +/- 0.02" w.c. to 12.0" w.c. (1.27 mm w.c. to 304.8 mm w.c.) (0 to 0.43 psi) |
Field Adjustable Release Range | 0.04" w.c. to 11.2" w.c. |
Approximate Switching Differential | Progressive, increasing from 0.02 +/- 0.01" w.c. at minimum set point to approximately 0.8" w.c. at maximum set point. |
Operating Temperature Range | -40F to 180F (-40 to 82C) |
Measure Media | Air,or combustion by-products that will not degrade silicone |
Maximum Pressure | 1/2 psi (0.03 bar) |
Electrical Rating | 300 VA pilot duty at 115 to 277 VAC, 15 amps noninductive to 277 VAC, 60 Hz |
Life | 100,000 cycles minimum at 1/2 psi maximum pressure each cycle and at maximum rated electrical load |
Download Product Information:
Cleveland Controls AFS-A Air Pressure Sensing Switch Technical Datasheet
Q & A: Ask the Questions, share answers