Bard HVAC MC4002 Lead/Lag Controller

Bard HVAC MC4002 Lead/Lag Controller
Images for general purposes only. Actual may be different than depicted.
Bard HVAC MC4002 Lead/Lag Controller Bard HVAC MC4002 Lead/Lag Controller

Bard HVAC MC4002 Lead/Lag Controller

SKU: MC4002
Rating:
Quantity Price Stock
16
Usually Ships 2 - 5 Days
$577.90     /ea
16
0
$0.00
0
$0.00
0
MC4002
Bard HVAC MC4002 Lead/Lag Controller

The MC4002 has 2 stages of cooling control available for each connected air conditioner. It is designed for systems with or without economizers and for systems with 2-stage or dual compressors. The 2nd stage available for each air conditioner permits complete and proper control when economizers are installed or when 2-stage or dual compressors are utilized. With the addition of a simple 2 wire humidity controller as an input signal, it can provide electric reheat dehumidification circuit. The controller can also be configured for use with heat pumps. (NOTE: The electric reheat dehumidification feature is not available when configured for heat pumps).
The MC4002, either in basic form or when equipped with optional alarm relay boards, is a fully functional controller with unique configurable capability. The MC4002 can be ordered as a basic controller only or factory equipped with one of two variations of alarm boards with varying amounts of alarm capabilities to fit the user’s requirements. Ethernet communication option is also available.
If only the base controller is initially installed, it can be easily upgraded by simple snap-in of the alarm relay board and plug-in of the communication cable to the main controller board. Form C dry contact alarm relays are used, offering both NO and NC switching to meet the user’s specific alarm protocol, providing complete flexibility to meet any user’s requirements. All alarm actuations are individually indicated on the controller front panel, along with indication for active stages of cooling or heating, and which unit is currently “lead”. A digital display indicates building temperature and is also used for all of the programming functions.

Features:

Controller:
  • Electronic (non-mercury) design
  • Programmable
  • Works with or without economizers
  •  Dehumidification control option
  •  Can be used with heat pumps
Alarm Boards:
  • Can be specified with or without alarm boards
  • Alarms boards can be added at any time
  • Alarm circuits can be NO or NC logic
Communication Board:
  • Ethernet remote access for all controller functions
  • Can be factory or field installed
  • IPV6 with SNMP traps
Ease of Installation:
  • Powered by 24V from A/C units
  • Phasing of 24V from units is not required
  • Durable metal enclosure adequately sized for ease of conduit and wire installation
Certifications & Approvals:
  • Complies with FCC Rule 15, Subpart B, Class A
  • This ISM device also complies w/Canadian ICES-001
  • Complies with CE Standards EN55011/EN50081 and EN55024 for ISM Equipment, Class A
  • ETL Conforms to UL916 Standard for Energy Management Equipment, Certified to CSA STD C22.2 No. 205
Lead/lag changeover time: 0 to 30 days
Timing accuracy: +/- 1%
Heating control stages: 1 for each A/C unit, 2 for each heat pump if so configured
Cooling control stages: 2 for each A/C unit (4 total)
Inter-stage differential: Adjustable
HVAC outputs: Form A (NO) relays (1A @ 24VAC)
Isolation circuitry: No line or low voltage phasing required
Digital Display: 4-character LCD
Cooling set point range: 65 to 90F (18 to 32C)
Temperature accuracy: +/- 1F from 60-85F (16-30C) +/- 1% outside 60-85F