The BAPI Resistance Output Module (ROM) is used on a Wireless System as a temperature data converter and for sending multiple variables to the controller. It converts data from 418 MHz or 900 MHz Receiver into resistance for the DDC controller. A wireless temperature transmitter that has a pushbutton and LED can be easily trained to ROM units.
Multiple Output Modules can be linked to a Receiver. Also, no need for calibration for it is factory calibrated to output a 10K-2, 10K-3, or 10K-3(11K) or 20K thermistor curve.
Quick and easy to install in surface, 2.75 Wide Snaptrack or in a 35mm DIN rail.
Material & Rating | ABS Plastic, UL94, V-0 |
---|---|
Environmental Operation Range (Humidity) | 5% to 95% RH non-condensing |
Environmental Operation Range (Temperature) | 32F to 140F (0C to 60C) |
Output Resolution | ~40Ω |
Bus Cable Distance | 4,000 ft with shielded, twisted pair cable (Belden 9841, Belden 8132 or equivalent) |
Lost Communication Timeout | 15 min. (Fast Flash) Reverts to High Resistance >35KΩ (Low Temperature) |
Analog Input Bias Voltage | 5 VDC max |
Power Consumption | 3 mA max. DC, .1 VA max AC |
Supply Power | 9 to 30 VDC or 17 to 31 VAC, half wave |
Temperature Output Ranges at ~0.5F Resolution | 10K-2 Unit:35ºF to 120ºF (1ºC to 50ºC); 10K-3 Unit: 32ºF to 120ºF (0ºC to 50ºC); 10K-3(11K) Unit: .32ºF to 120ºF (0ºC to 50ºC); 20K Unit: 53ºF to 120ºF (12ºC to 50ºC) |